Installation The flexibility of the modular system allows for simple installation of single or multipoint gas detection systems. Each point of detection requires the installation of one sensor/transmitter and one receiver module. The sensor/ transmitter is installed in the area to be monitored and the receiver module can be located up to 1000 feet away. A power supply module, sufficient for use with up to two receivers, is housed with the Receivers in a NEMA 4X enclosure. All enclosures are provided with knockouts on all four sides to facilitate wiring using the 1/2" FNPT (12.7 mm) conduit hubs provided. Equally suitable for indoor or outdoor applications, these NEMA 4Xrated polystyrene enclosures are fitted with a tough hinged polycarbonate window for clear visibility of all indicators and easy access to the control panel. Included within the enclosure is a piezoelectric horn to provide audible local warning. Technical Data Gases Detected Chlorine, Sulfur Dioxide, Ammonia Power Requirements 85-255 VAC, 50/60 HZ 1 Amp - Self-regulating Ambient Temperature 0° to 105°F (-18° to 40°C) continuous -10° to 120°F (-23° to 49°C) intermittent Humidity 0-99% non-condensing Gas Alarm Setpoints 2 independent setpoints Warning Level - adjustable from 5% to 100% of range Alarm Level - adjustable from 5% to 100% of range Alarm Indicators High intensity LED bars Function - WARNING indicator non-latching - Alarm indicator latching Alarm Relays Three assignable alarm relays for either alarm setpoint 10A at 120 VAC, 5A at 250 VAC, resistive, SPDT configurable for normal/fail-safe, latching/nonlatching, and fast/slow operation Alarm Relay and Indicator Reset Activated from front panel switch or through remote reset. Sensor Alarm Indicates loss of sensor/transmitter input or failure of Optional sensor Auto-Test. Sensor Alarm Relay and Indicator Front panel LED indicator and relay; 10A, at 120 VAC, 5A at 250 VAC, resistive SPDT factory set to fail-safe operation. Monitor Concentration Display 4-digit LED, sunlight readable. Monitor Concentration Output Signal Isolated 4-20 mA DC, 1000 ohms maximum load. Power Supply Output Voltage Regulated 13.7 VDC, 1A supplied to 1 or 2 receivers. Also, for recharging external battery, audible back-up and for integral Alarm horn power. Audible Alarm Horn Weatherproof 12 VDC piezoelectric horn 85-dB output Signal for local alarming. Power Failure Alarm Relay Loss of AC input power. 1 relay 10A at 120 VAC, 5A at 250 VAC, SPDT resistive. Enclosure NEMA 4X Polystyrene with knockouts on four sides for 1/2” (12.7 mm) FNPT conduit hubs. Four single point enclosure -4 conduit hubs are provided. Four dual point enclosure -7 conduit hubs are provided. Gas Sensor Type Electrochemical gas diffusion Gas Sensor Connection Distance Up to 1000 feet (300 m) to receiver. Two wire cable. For a dual point unit, 50 ft. (15 m) of cable is provided. For a single point unit, 25 ft. (8 m) of cable is provided. Sensor Operating Life 2 years Sensor Storage Life 1 year
|