Input |
|
Resistance thermometer |
|
Measured variable |
Temperature |
Sensor type |
|
|
Pt25 … Pt1000 |
- To JIS C 1604; a = 0.00392 K-1
|
Pt25 … Pt1000 |
|
Ni25 … Ni1000 |
|
over special characteristic (max. 30 points) |
Sensor factor |
0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000) |
Units |
°C or °F |
Connection |
|
|
1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system |
- Generation of average value
|
2 identical resistance thermometers in 2-wire system for generation of average temperature |
|
2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1) |
Interface |
|
|
Parameterizable line resistance ≤ 100 Ω (loop resistance) |
|
No balancing required |
|
No balancing required |
Sensor current |
≤ 0.45 mA |
Response time |
≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring |
can be switched off |
Short-circuit monitoring |
can be switched off (value is adjustable) |
Measuring range |
Parameterizable (see table "Digital measuring errors") |
Min. measured span |
10 °C (18 °F) |
Characteristic curve |
Temperature-linear or special characteristic |
Resistance-based sensors |
|
Measured variable |
Actual resistance |
Sensor type |
Resistance-based, potentiometers |
Units |
Ω |
Connection |
|
|
1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system |
- Generation of average value
|
2 resistance-based sensors in 2-wire system for generation of average value |
|
2 resistance thermometers in 2-wire system (R1 – R2 or R2 – R1) |
Interface |
|
|
Parameterizable line resistance ≤ 100 Ω (loop resistance) |
|
No balancing required |
|
No balancing required |
Sensor current |
≤ 0.45 mA |
Response time |
≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring |
can be switched off |
Short-circuit monitoring |
can be switched off (value is adjustable) |
Measuring range |
Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors") |
Min. measured span |
5 Ω ... 25 Ω (see Table "Digital measuring errors") |
Characteristic curve |
Resistance-linear or special characteristic |
Thermocouples |
|
Measured variable |
Temperature |
Sensor type (thermocouples) |
|
|
Pt30Rh-Pt6Rh to DIN IEC 584 |
|
W5 %-Re acc. to ASTM 988 |
|
W3 %-Re acc. to ASTM 988 |
|
NiCr-CuNi to DIN IEC 584 |
|
Fe-CuNi to DIN IEC 584 |
|
NiCr-Ni to DIN IEC 584 |
|
Fe-CuNi to DIN 43710 |
|
NiCrSi-NiSi to DIN IEC 584 |
|
Pt13Rh-Pt to DIN IEC 584 |
|
Pt10Rh-Pt to DIN IEC 584 |
|
Cu-CuNi to DIN IEC 584 |
|
Cu-CuNi to DIN 43710 |
Units |
°C or °F |
Connection |
|
|
1 thermocouple (TC) |
- Generation of average value
|
2 thermocouples (TC) |
|
2 thermocouples (TC) TC1 – TC2 or TC2 – TC1) |
Response time |
≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring |
can be switched off |
Cold junction compensation |
|
|
With integrated Pt100 resistance thermometer |
|
With external Pt100 IEC 60571 (2-wire or 3-wire connection) |
|
Cold junction temperature can be set as fixed value |
Measuring range |
Parameterizable (see table "Digital measuring errors") |
Min. measured span |
Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors") |
Characteristic curve |
Temperature-linear or special characteristic |
mV sensor |
|
Measured variable |
DC voltage |
Sensor type |
DC voltage source (DC voltage source possible over an externally connected resistor) |
Units |
mV |
Response time |
≤ 250 ms for 1 sensor with open-circuit monitoring |
Open-circuit monitoring |
can be switched off |
Short-circuit monitoring |
can be switched off (value is adjustable) |
Measuring range |
-10 ... +70 mV -100 +1100 mV |
Min. measured span |
2 mV or 20 mV |
Overload capability of the input |
-1.5 ... +3.5 V DC |
Input resistance |
≥ 1 MΩ |
Characteristic curve |
Voltage-linear or special characteristic |
Output |
|
Output signal |
4 ... 20 mA, 2-wire |
Auxiliary power supply |
11 ... 35 V DC (to 30 V with EEx) |
Max. load |
(Uaux – 11 V)/0.023 A |
Overrange |
3.6 ... 23 mA, infinitely adjustable (default range: 3.80 mA ... 20.50 mA) |
Error signal (e.g. in the event of sensor breakage) |
3.6 ... 23 mA, infinitely adjustable (default value: 22.8 mA) |
Sample cycle |
0.25 s nominal |
Damping |
Software filter 1st order 0 ... 30 s (parameterizable) |
Protection |
Against reversed polarity |
Electrically isolated |
Input against output (1 kVeff) |
Measuring accuracy |
|
Digital measuring errors |
See Table "Digital measuring errors" |
Reference conditions |
|
|
24 V ± 1 % |
|
500 Ω |
|
23 °C |
|
> 5 min |
Error in the analog output (digital/analog converter) |
< 0.1 % of span |
Error due to internal cold junction |
< 0.5 °C (0.9 °F) |
Temperature effect |
< 0.1 % of max. span/10 °C (18 °F) |
Auxiliary power supply effect |
< 0.005 % of span/V |
Effect of load impedance |
< 0.012 % of span/100 Ω |
Long-term drift |
|
|
< 0.02 % of max. span |
|
< 0.03 % of max. span |
|
< 0.04 % of max. span |
Conditions of use |
|
Ambient conditions |
|
Ambient temperature range |
-40 ... +85 °C (-40 ... 185 °F) |
Storage temperature range |
-40 ... +85 °C (-40 ... 185 °F) |
Relative humidity |
< 98 %, with condensation |
Electromagnetic compatibility |
acc. to EN 61326 and NE21 |
Construction |
|
Material |
Molded plastic |
Weight |
50 g (0.11 lb) |
Dimensions |
See "Dimensional drawings" |
Cross-section of cables |
Max. 2.5 mm² (AWG 13) |
Degree of protection to IEC 60529 |
|
|
IP40 |
|
IP00 |
Certificates and approvals |
|
Explosion protection ATEX |
|
EC type test certificate |
PTB 05 ATEX 2040X |
- "Intrinsic safety" type of protection
|
II 1 G Ex ia IIC T6/T4 II 2(1) G Ex ib/ia IIC T6/T4 |
- "Operating equipment that is non-ignitable and has limited energy" type of protection
|
II 3 G Ex nL IIC T6/T4 II 3 G Ex nA IIC T6/T4 |
Explosion protection: FM for USA |
|
|
FM 3024169 |
|
IS/Cl I, II, III/Div 1/GP ABCDEFG T6, T5, T4
IS/Cl I/ZN 0/AEx ia IIC T6, T5, T4
NI/Cl I, II, III/Div 2/GP ABCDFG T6, T5, T4
NI/Cl I/ZN 2/IIC T6, T5, T4 |
Explosion protection to FM for Canada (cFMUS) |
|
|
FM 3024169C |
|
IS/Cl I/ZN 0/Ex ia IIC T6, T5, T4
NI/Cl I/ZN 2/Ex nAL IIC T6, T5, T4 |
Software requirements for SIPROM T |
|
PC operating system |
Windows ME, 2000 and XP; also Windows 95, 98 and 98 SE, but only in connection with RS 232 modem. |