   PRODUCT: 
SITRANS TR200



Code: 7NG3032-0JN00
Product name: SITRANS TR200

Ultra flexible - with the universal SITRANS TR200 transmitte

  

Input

 

Resistance thermometer

 

Measured variable

Temperature

Sensor type

 
  • To IEC 60751

Pt25 … Pt1000

  • To JIS C 1604; a=0.00392 K-1

Pt25 … Pt1000

  • To IEC 60751

Ni25 … Ni1000

  • Special type

over special characteristic (max. 30 points)

Sensor factor

0.25 ... 10 (adaptation of the basic type, e.g. Pt100 to version Pt25 ... Pt1000)

Units

°C or °F

Connection

 
  • Standard connection

1 resistance thermometer (RTD) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 identical resistance thermometers in 2-wire system for generation of average temperature

  • Generation of difference

2 identical resistance thermometers (RTD) in 2-wire system (RTD 1 – RTD 2 or RTD 2 – RTD 1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Always active (cannot be disabled)

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

10 °C (18 °F)

Characteristic curve

Temperature-linear or special characteristic

Resistance-based sensors

 

Measured variable

Actual resistance

Sensor type

Resistance-based, potentiometers

Units

Ω

Connection

 
  • Normal connection

1 resistance-based sensor (R) in 2-wire, 3-wire or 4-wire system

  • Generation of average value

2 resistance-based sensors in 2-wire system for generation of average value

  • Generation of difference

2 resistance thermometers in 2-wire system
(R1 – R2 or R2 – R1)

Interface

 
  • Two-wire system

Parameterizable line resistance ≤ 100 Ω (loop resistance)

  • Three-wire system

No balancing required

  • Four-wire system

No balancing required

Sensor current

≤ 0.45 mA

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

Always active (cannot be disabled)

Short-circuit monitoring

can be switched off (value is adjustable)

Measuring range

Parameterizable, max. 0 ... 2200 Ω (see Table "Digital measuring errors")

Min. measured span

5 Ω ... 25 Ω (see Table "Digital measuring errors")

Characteristic curve

Resistance-linear or special characteristic

Thermocouples

 

Measured variable

Temperature

Sensor type (thermocouples)

 
  • Type B

Pt30Rh-Pt6Rh to DIN IEC 584

  • Type C

W5 %-Re acc. to ASTM 988

  • Type D

W3 %-Re acc. to ASTM 988

  • Type E

NiCr-CuNi to DIN IEC 584

  • Type J

Fe-CuNi to DIN IEC 584

  • Type K

NiCr-Ni to DIN IEC 584

  • Type L

Fe-CuNi to DIN 43710

  • Type N

NiCrSi-NiSi to DIN IEC 584

  • Type R

Pt13Rh-Pt to DIN IEC 584

  • Type S

Pt10Rh-Pt to DIN IEC 584

  • Type T

Cu-CuNi to DIN IEC 584

  • Type U

Cu-CuNi to DIN 43710

Units

°C or °F

Connection

 
  • Standard connection

1 thermocouple (TC)

  • Generation of average value

2 identical thermocouples (TC)

  • Generation of difference

2 identical thermocouples (TC) TC1 – TC2 or TC2 – TC1

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Cold junction compensation

 
  • Internal

With integrated Pt100 resistance thermometer

  • External

With external Pt100 IEC 60571 (2-wire or 3-wire connection)

  • External fixed

Cold junction temperature can be set as fixed value

Measuring range

Parameterizable (see table "Digital measuring errors")

Min. measured span

Min. 50 ... 100 °C (90 ... 180 °F) (see table "Digital measuring errors")

Characteristic curve

Temperature-linear or special characteristic

mV sensor

 

Measured variable

DC voltage

Sensor type

DC voltage source (DC voltage source possible over an externally connected resistor)

Units

mV

Response time T63

≤ 250 ms for 1 sensor with open-circuit monitoring

Open-circuit monitoring

can be switched off

Measuring range

Parameterizable max. -100 … 1100 mV

 

Share |
Video clips
Hot News
Certificates
Online Support
Sales Support
0901 185 205
Support via Skype     Support via Yahoo Messanger    
Technical Support
0938 77 40 99
Support via Skype     Support via Yahoo Messanger    
 
An Thinh Automation Ltd.,
26/50 Nguyen Minh Hoang street, Tan Binh District, HCM City, Viet Nam
Tel:(84) 08 3948 1715         Fax: (84) 08 3811 1332