   PRODUCT: 
MAG 5000/6000



Code: 7ME6910/7ME6920
Product name: MAG 5000/6000

Bộ hiển thị và điều khiển MAG 5000/6000 loại gắn liền (Trái) and 19“ loại gắn trên tủ (phải)

 

Mode of operation and design

 

Measuring principle

Electromagnetic with pulsed constant field

Empty pipe

Detection of empty pipe (special cable required in remote mounted installation)

Excitation frequency

Depend on sensor size

Electrode input impedance

> 1 x 1014 Ω

Input

 

Digital input

11 ... 30 V DC, Ri = 4. 4 KΩ

  • Activation time

50 ms

  • Current

IDC 11 V = 2.5 mA, IDC 30 V = 7 mA

Output

 

Current output

 
  • Signal range

0 ... 20 mA or 4 ... 20 mA

  • Load

< 800 Ω

Time constant

0.1 … 30 s, adjustable

Digital output

 
  • Frequency

0 ... 10 kHz, 50 % duty cycle (uni/bidirectional)

  • Pulse (active)

DC 24 V, 30 mA, 1 KΩ ≤ Ri ≤ 10 KΩ, short-circuit-protected (power supplied from flowmeter)

  • Pulse (passive)

DC 3 … 30 V, max. 110 mA, 200 Ω ≤ Ri ≤ 10 KΩ (powered from connected equipment)

  • Time constant

0.1 … 30 s, adjustable

Relay output

 
  • Time constant

Changeover relay, same as current output

  • Load

42 V AC/2 A, 24 V DC/1 A

Low flow cut off

0 ... 9.9 % of maximum flow

Galvanic isolation

All inputs and outputs are galvanically isolated

Max. measuring error (incl. sensor and zero point)

 
  • MAG 5000

0.5 % of rate

  • MAG 6000

0.25 % of rate

Rated operation conditions

 

Ambient temperature

 
  • Operation
  • Display version:

-20 ... +50  C (-4 ... +122  F)

  • Blind version:

-20 ... +60  C (-4 ... +140  F)

  • Storage

-40 ... +70  C (-40 ... +158 F°)

Mechanical load

 
  • Compact version

18 ... 1000 Hz, 3,17 G rms, sinusoidal in all directions to IEC 68-2-36

  • 19“ insert

1 ... 800 Hz, 1 G, sinusoidal in all directions to

IEC 68-2-36

Degree of protection

 
  • Compact version

IP67/NEMA 4X to IEC 529 and DIN 40050 (1 mH2O 30 min.)

  • 19“ insert

IP20/NEMA 2 to IEC 529 and DIN 40050

EMC performance

EN 61326-1 (all environments)

EN 61326-2-5

Display and keypad

 

Totalizer

Two eight-digit counters for forward, net or reverse flow

Display

Background illumination with alphanumeric text, 3 x 20 characters to indicate flow rate, totalized values, settings and faults; Reverse flow indicated by negative sign

  • Time constant

Time constant as current output time constant

Design

 

Enclosure material

 
  • Compact version

Fiber glass reinforced polyamide; optional (IP67 only):
AISI 316 stainless steel

  • 19“-insert

Standard 19“ insert of aluminium/steel (DIN 41494), width: 21 TE, height: 3 HE

  • Back of panel

IP20/NEMA 2; Aluminium

  • Panel mounting

IP65/NEMA 4; ABS plastic

  • Wall mounting

IP66/NEMA 4; ABS plastic

Dimensional drawings

 
  • Compact version

See dimensional drawings

  • 19“ insert

See dimensional drawings

Weight

 
  • Compact version

0.75 kg (2 lbs)

  • 19“ insert

See dimensional drawings

Power supply

  • 115 ... 230 V AC  +10 % -15 %, 50 ... 60 Hz, 17 VA
  • 11 ... 30 V DC or 11 ... 24 V AC

Power consumption

  • 230 V AC: 17 VA
  • 24 V AC : 9 W, I= 380 mA, IST = 8 A (30 ms)
  • 12 V DC : 11 W, I= 920 mA, IST = 4 A (250 ms)

Certificates and approvals

CE, ULc general purpose, C-tick; CSA/FM Class 1, div 2

Custody transfer approval (MAG 5000/6000 CT)

  • PTB OIML R49 (cold water pattern approval); MI-001
  • PTB and DANAK OIML R75 (hot water pattern approval) (MAG 6000 CT)
  • PTB and DANAK OIML R117 (cold water/milk, beer etc. pattern approval) (MAG 6000 CT)

Communication

 

Standard

 
  • MAG 5000

Without serial communication or HART as option

  • MAG 6000

Prepared for client mounted add-on modules

Optional (On MAG 6000 only)

HART, MODBUS RTU/RS485, FOUNDATION Fieldbus H1, DeviceNet, PROFIBUS PA, PROFIBUS DP as add-on modules

  • MAG 5000/6000 CT

no communication moduls approved


Safety barrier (e/ia)
 

Application

For use with MAG 5000/6000 19” and MAG 1100 Ex ATEX/MAG 3100 Ex ATEX

 

Ex approval

MAG 1100 Ex [EEx e ia] IIB ATEX

MAG 3100 Ex [EEx e ia] IIC ATEX

Cable parameter

  • Electrode

Group

Capacity in μF

Inductance in mH

IIC

≤ 4.1

≤ 80

IIB

≤ 45

≤ 87

IIA

≤ 45

≤ 87

 

Share |
Video clips
Hot News
Certificates
Online Support
Sales Support
0901 185 205
Support via Skype     Support via Yahoo Messanger    
Technical Support
0938 77 40 99
Support via Skype     Support via Yahoo Messanger    
 
An Thinh Automation Ltd.,
26/50 Nguyen Minh Hoang street, Tan Binh District, HCM City, Viet Nam
Tel:(84) 08 3948 1715         Fax: (84) 08 3811 1332