Input |
|
Selectable filters to suppress the line frequency |
50 Hz, 60 Hz, also 10 Hz for special applications (line frequency filter is similar with measuring frequency) |
Resistance thermometer |
|
Measured variable |
Temperature |
Measured range |
Parameterizable |
Measured span |
Min. 25 °C (45 °F) x 1/scaling factor |
Sensor type |
|
|
Pt100 (DIN IEC 751) |
|
Pt100 (JIS C1604-81) |
|
Ni100 (DIN 43760) |
- Special type (RRTD ≤ 500 Ω)
|
Multiples or parts of the defined characteristic values can be parameterized (e.g. Pt500, Ni120) |
Voltage measurement |
Temperature-linear, resistance-linear or customer-specific |
Type of connection |
- Normal connection
- Sum or parallel connection
- Mean-value or differential connection
|
Connection |
2, 3 or 4-wire circuit |
Measuring range limits |
Depending on type of connected thermometer (defined range of resistance thermometer) |
Sensor breakage monitoring |
Monitoring of all connections for open-circuit (function can be switched off) |
Sensor short-circuit monitoring |
Parameterizable response threshold (function can be switched off) |
Resistance-based sensors, potentiometers |
|
Measured variable |
Ohmic impedance |
Measured range |
Parameterizable |
Measured span |
Min. 10 Ω |
Voltage measurement |
Resistance-linear or customer-specific |
Type of connection |
- Normal connection
- Differential connection
- Mean-value connection
|
Connection |
2, 3 or 4-wire circuit |
Input range |
0 ... 6000 Ω;
with mean-value and difference circuits: 0 ... 3000 Ω |
Sensor breakage monitoring |
Monitoring of all connections for open-circuit (function can be switched off) |
Sensor short-circuit monitoring |
Parameterizable response threshold (function can be switched off) |
Thermocouple elements |
|
Measured variable |
Temperature |
Measured range |
Parameterizable |
Measured span |
Min. 50 °C (32.22 °C) x 1/scaling factor |
Measuring range limits |
Depend. on type of thermocouple element |
Thermocouple |
Type B: Pt30 %Rh/Pt6 %Rh (DIN IEC 584) |
|
Type C W5 %-Re (ASTM 988) |
|
Type D W3 %-Re (ASTM 988) |
|
Type E: NiCr/CuNi (DIN IEC 584) |
|
Type J: Fe/CuNi (DIN IEC 584) |
|
Type K: NiCr/Ni (DIN IEC 584) |
|
Type L Fe-CuNi (DIN 43710) |
|
Type N: NiCrSi-NiSi (DIN IEC 584) |
|
Type R: Pt13 %Rh/Pt (DIN IEC 584) |
|
Type S: Pt10 %Rh/Pt (DIN IEC 584) |
|
Type T: Cu/CuNi (DIN IEC 584) |
|
Type U: Cu/CuNi (DIN 43710) |
|
Special type (-10 mV ≤ UTC ≤ 100 mV) |
Voltage measurement |
Temperature-linear, voltage-linear or customer-specific |
Type of connection |
- Normal connection
- Sum connection
- Mean-value connection
- Differential connection
|
Cold junction compensation |
None, internal measurement, external measurement or predefined fixed value |
Sensor breakage monitoring |
Function can be switched off |
mV sensors |
|
Measured variable |
DC voltage |
Measured range |
Parameterizable |
Measured span |
Min. 4 mV |
Input range |
-120 ... +1000mV |
Voltage measurement |
Voltage-linear or customer-specific |
Overload capacity of inputs |
Max. ± 3.5 V |
Input resistance |
≥ 1 Ω |
Sensor current |
Approx. 180 μA |
Sensor breakage monitoring |
Function can be switched off |
V sources |
|
Measured variable |
DC voltage |
Measured range |
Parameterizable |
Voltage measurement |
Voltage-linear or customer-specific |
Input range/min. span |
|
- Devices with 7NG3242-xxxx1 or 7NG3242-xxxx 0 with U/I plug
|
-1.2 V ... +10 V 0.04 V |
- Devices with 7NG3242-xxxx2
|
-12 V ... +100 V 0.4 V |
- Devices with 7NG3242-xxxx3
|
-120 V ... +140 V 4.0 V |
Sensor breakage monitoring |
Not possible |
μA, mA sources |
|
Measured variable |
DC voltage |
Measured range |
Parameterizable |
Voltage measurement |
Current-linear or customer- specific |
Input range/min. span |
|
- Devices with 7NG3242-xxxx4
|
-12 μA ... +100 μA/0.4 μA |
- Devices with 7NG3242-xxxx5
|
-120 μA ... +1000 μA/4 μA |
- Devices with 7NG3242-xxxx6
|
-1.2 mA ... +10 mA 0.04 mA |
- Devices with 7NG3242-xxxx7 or 7NG3242-xxxx 0 with U/I plug
|
-12 mA ... +100 mA 0.4 mA |
- Devices with 7NG3242-xxxx8
|
-120 mA ... +1000 mA 4 mA |
Sensor breakage monitoring |
Not possible |
Output |
|
Output signal |
Load-independent direct current 0/4 ... 20 mA, can be switched to load-independent DC voltage 0/2 ... 10 V using plug-in jumpers. |
Current 0/4 ... 20 mA |
|
|
-0.5 ... +23.0 mA, continuously adjustable |
- Output range following sensor fault
|
-0.5 ... +23.0 mA, continuously adjustable |
|
≤ 650 Ω |
|
≤ 30 V |
Voltage 0/2 ... 10 V |
|
|
-0.25 ... +10.75 V, continuously adjustable |
- Output range following sensor fault
|
-0.25 ... +10.75 V, continuously adjustable |
|
≥ 1 kΩ |
|
≤ 10 nF |
|
≤ 100 mA (not permanently short-circuit-proof) |
|
|
- Adjustable time constant T63
|
0 ... 100 s, in steps of 0.1 s |
- Current source/voltage source
|
Continuously adjustable within the total operating range |
Sensor fault/limit signalling |
By operation indicator, relay output or HART interface |
Operation indicator |
Flashing signal |
|
Flashing frequency 5 Hz |
|
Flashing frequency 1 Hz |
Relay output |
Either as NO or NC contact with 1 changeover contact |
|
≤ 150 W, ≤ 625 VA |
|
≤ 125 V DC, ≤ 250 V AC |
|
≤ DC 2.5 A |
Overrange |
Signalling of sensor or line breakage and sensor short-circuit |
Limit monitoring |
|
|
0 ... 10 s |
- Monitoring functions of limit module
|
- Sensor fault (breakage and/or short-circuit)
- Lower and upper limit
- Window (combination of lower and upper limits)
- Limit and sensor fault detection can be combined
|
|
Parameterizable between 0 and 100 % of measuring range |
Power supply |
|
Universal power supply unit |
115/230 V AC/DC or 24 V AC/DC |
Tolerance range for power supply |
|
|
80 ... 300 V DC; 90 ... 250 V AC |
|
18 ... 80 V DC; 20.4 ... 55.2 V AC (in each case interruption-resistant up to 20 ms in the complete tolerance range) |
Tolerance range for mains frequency |
47 ... 63 Hz |
Power consumption with |
|
|
≤ 5 VA |
|
≤ 5 W |
|
≤ 5 VA |
|
≤ 5 W |
Electrical isolation |
|
Electrically isolated circuits |
Input, output, power supply and sensor fault/limit monitoring output are electrically isolated from one another. The HART interface is electrically connected to the output. |
Working voltage between all electrically isolated circuits |
The voltage U eff between any two terminals must not exceed 300 V |
Measuring accuracy |
|
Measurement error |
|
- Error in the internal cold junction
|
≤ 3 °C ± 0,1 °C/10 °C (≤ 5.4 °F ± 0,18 °F/18 °F) |
- Error of external cold junction terminal 7NG3092-8AV
|
≤ 0.5 °C ± 0,1 °C/10 °C (≤ 0.9 °F ± 0.18 °F/18 °F) |
|
See "Digital error" |
|
≤ 0.05 % of span in addition to digital error |
Influencing effects (referred to the digital output) |
Compared to the max. span: |
|
≤ 0.08 %/10 °C (≤ 0.08 %/18 °F)
≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) |
|
≤ 0.1 %/year |
Influencing effects referred to the analog output IAN or UAN |
Compared to the span: |
|
≤ 0.08 %/10°C (≤ 0.08 %/18 °F)
≤ 0.2 % in the range -10 ... +60 °C (14 ... 140 °F) |
|
≤ 0.05 %/10 V |
|
≤ 0.05 % with change from 50 ... 650 Ω |
|
≤ 0.1 % with change in load current from 0 … 10 mA |
- Long-term drift (start-of-scale value, span)
|
≤ 0.03 %/month |
Response time (T63 without electrical damping) |
≤ 0.2 s |
Electromagnetic compatibility |
According to EN 61 326 and NAMUR NE21 |
Certificate and approvals |
|
ATEX |
To DIN EN 50014: 1997, EN 50020: 1994 |
Intrinsic safety to EN 50 020 |
|
|
II (1) G D [EEx ia/ib ] IIB |
|
II (1) G D [EEx ia/ib ] IIC |
EC-Type Examination Certificate |
TÜV (German Technical Inspectorate) 01 ATEX 1675 |
Rated conditions |
|
Installation conditions |
|
Location (for devices with explosion protection) |
|
|
Outside the potentially explosive atmosphere |
|
Within the potentially explosive atmosphere zone 1 (also in zone 0 in conjunction with the prescribed protection requirements for the sensor) |
Ambient conditions |
|
Permissible ambient temperature |
-25 ... +70 °C (-13 ... +158 °F) |
Permissible storage temperature |
-40 ... +85 °C (-40 ... +185 °F) |
Climatic class |
|
|
5 ... 95 %, no condensation |
Design |
|
Weight |
Approx. 0.24 kg (0.53 lb) |
Enclosure material |
PBT, glass-fibre reinforced |
Degree of protection to IEC 529 |
IP20 |
Degree of protection to VDE 0100 |
Protection class I |
Type of installation |
35-mm top hat rail (1.38 inch) (DIN EN 50022) or 32-mm G-type rail (1.26 inch) (DIN EN 50035) |
Electrical connection / process connection |
Screw plug connectors, max. 2.5 mm² (0.01 inch²) |
Parameterization interface |
|
Protocol |
HART, version 5.9 |
Load with connection of |
|
|
230 ... 650 Ω |
|
230 ... 500 Ω |
Software for PC/laptop |
SIMATIC PDM version V5.1 and later |