Mã sản phẩm:
7NG3214/7NG3215
Tên sản phẩm:
SITRANS TH400, fieldbus transmitters
|
The SITRANS TH400 temperature transmitter is a small field bus transmitter for mounting in the connection head of form B.
|
Input |
|
Analog-to-digital conversion |
|
|
< 50 ms |
|
24-bit |
Resistance thermometer |
|
Pt25 ... Pt1000 to IEC 60751/JIS C 1604 |
|
|
-200 ... +850 °C (-328 ... +1562 °F) |
Ni25 ... Ni1000 to DIN 43760 |
|
|
-60 ... +250 °C (-76 ... +482 °F) |
Cu10 ... Cu1000, α = 0.00427 |
|
|
-50 ... +200 °C (-58 ... +392 °F) |
Line resistance per sensor cable |
Max. 50 Ω |
Sensor current |
Nominal 0.2 mA |
Sensor fault detection |
|
|
Yes |
- Sensor short-circuit detection
|
Yes, < 15 Ω |
Resistance-based sensors |
|
Measuring range |
0 Ω ... 10 kΩ |
Line resistance per sensor cable |
Max. 50 Ω |
Sensor current |
Nominal 0.2 mA |
Sensor fault detection |
|
|
Yes |
- Sensor short-circuit detection
|
Yes, < 15 Ω |
Thermocouple |
|
to IEC 584 |
Measuring range |
|
400 ... 1820 °C (752 ... 3308 °F) |
|
-100 ... +1000 °C (-148 ... +1832 °F) |
|
-100 ... +1000 °C (-148 ... +1832 °F) |
|
-100 ... +1200 °C (-148 ... +2192 °F) |
|
-180 ... +1300 °C (-292 ... +2372 °F) |
|
-50 ... +1760 °C (-58 ... +3200 °F) |
|
-50 ... +1760 °C (-58 ... +3200 °F) |
|
-200 ... +400 °C (-328 ... +752 °F) |
to DIN 43710 |
|
|
-200 ... +900 °C (-328 ... +1652 °F) |
|
-200 ... +600 °C (-328 ... +1112 °F) |
to ASTM E988-90 |
|
|
0 ... 2300 °C (32 ... +4172 °F) |
|
0 ... 2300 °C (32 ... +4172 °F) |
External cold junction compensation |
-40 ... +135 °C (-40 ... +275 °F) |
Sensor fault detection |
|
|
Yes |
- Sensor short-circuit detection
|
Yes, < 3 mV |
- Sensor current in the event of open-circuit monitoring
|
4 μA |
mV sensor - voltage input |
|
Measuring range |
-800 ... +800 mV |
Input resistance |
10 MΩ |
Output |
|
Filter time (programmable) |
0 ... 60 s |
Update time |
< 400 ms |
Measuring accuracy |
|
|
Accuracy is defined as the higher value of general values and basic values. |
General values |
|
|
Type of input |
Absolute accuracy |
Temperature coefficient |
All |
≤ ±0.05 % of measured value |
≤ ±0.002 % of measured value / °C |
Basic values |
|
|
Type of input |
Basic accuracy |
Temperature coefficient |
Pt100 and Pt1000 |
≤± 0.1 °C |
≤± 0.002 °C / °C |
Ni100 |
≤± 0.15 °C |
≤± 0.002 °C / °C |
Cu10 |
≤± 1.3 °C |
≤± 0.02 °C / °C |
Resistance-based sensors |
≤± 0.05 °Ω |
≤± 0.002 °Ω / °C |
Voltage source |
≤± 10 μV |
≤± 0.2 % μV / °C |
Thermocouple, type: E, J, K, L, N, T, U |
≤± 0.5 °C |
≤± 0.01 °Ω / °C |
Thermocouple, type: B, R, S, W3, W5 |
≤± 1 °C |
≤± 0.025 % °C / °C |
Cold junction compensation |
≤± 0.5 °C |
|
Reference conditions |
|
|
Warming-up time |
30 s |
|
Signal-to-noise ratio |
Min. 60 dB |
|
Calibration condition |
20 ... 28 °C (68 ... 82 °F) |
|
Conditions of use |
|
Ambient conditions |
|
Permissible ambient temperature |
-40 ... +85 °C (-40 ... +185 °F) |
Permissible storage temperature |
-40 ... +85 °C (-40 ... +185 °F) |
Relative humidity |
≤ 98 %, with condensation |
Electrically isolated |
|
|
Input against output 1 kVeff |
|
Input against output 500 Veff |
Mechanical testing |
|
- Vibrations (DIN class B) to
|
IEC 60068-2-6 and IEC 60068-2-64 4 g/2 ... 100 Hz |
Electromagnetic compatibility |
|
EMC noise voltage influence |
< ±0.1 % of span |
Extended EMC noise immunity: NAMUR NE 21, criterion A, Burst |
< ±1 % of span |
EMC 2004/108/EC Emission and Noise Immunity to |
EN 61326 |
Construction |
|
Material |
Molded plastic |
Weight |
55 g (0.12 lb) |
Dimensions |
See Dimensional drawings |
Cross-section of cables |
Max. 2.5 mm2 (AWG 13) |
Degree of protection |
|
|
IP40 |
|
IP00 |
Auxiliary power supply |
|
Power supply |
|
- Standard, Ex "nA", Ex "nL", NI
|
9.0 ... 32 V DC |
|
9.0 ... 30 V DC |
- In FISCO/FNICO installations
|
9.0 ... 17.5 V DC |
Power consumption |
< 11 mA |
Max. increase in power consumption in the event of a fault |
< 7 mA |
Certificates and approvals |
|
Explosion protection ATEX |
|
EC type test certificate |
KEMA 06 ATEX 0264 X |
- "Intrinsic safety" type of protection
|
II 1 GD EEx ia IIC T4 ... T6 T65 °C ... T105 °C
II 2(1) GD EEx ib [ia] IIC T4 ... T6 T65 °C ... T105 °C |
EC type test certificate |
KEMA 06 ATEX 0263 X |
- Type of protection for "equipment is non-arcing"
|
II 3 G EEx nA [nL] IIC T4 ... T6 II 3 G EEx nL IIC T4 ... T6 |
Explosion protection: FM for USA |
|
|
FM 3027985 |
|
- IS/Cl I/Div 1/Groups ABCD T4, T5, T6, FISCO
- IS/Cl I/ZN 0/AEx ia, IIC T4, T5, T6, FISCO
- NI/Cl I/Div 2/Groups ABCD T4, T5, T6, FNICO
|
Explosion protection CSA for Canada |
|
|
CSA 1861385 |
|
- IS/Cl I/Div 1/Groups ABCD T4, T5, T6
- Ex ia IIC T4/T5/T6
Ex ib [ia] IIC T4/T5/T6
- Cl I/Div 2/Groups ABCD, T4, T5, T6
- Ex nA IIC T4/T5/T6
Cl I/ZN 2/AEx nA II T4, T5, T6 |
Communication |
|
Parameterization interface |
|
|
|
|
Profile 3.0 |
|
126 |
- FOUNDATION fieldbus connection
|
|
|
FF protocol |
|
Basic or LAS |
|
ITK 4.6 |
|
2 x analog and 1 x PID |
Factory setting |
only for SITRANS TH400 PA |
|
Sensor |
Pt100 (IEC) |
Type of connection |
3-wire circuit |
Unit |
°C |
Failure mode |
Last valid value |
Filter time |
0 s |
PA address |
126 |
PROFIBUS Ident No. |
Manufacturer-specific |
only for SITRANS TH400 FF |
|
Sensor |
Pt100 (IEC) |
Type of connection |
3-wire circuit |
Unit |
°C |
Failure mode |
Last valid value |
Filter time |
0 s |
Node address |
22 |
|
|
|
|
|
|
Sales Support |
|