Input |
|
Measuring range limits |
See “Dimensional drawings” |
Media pressure |
1 ... 100 bar (Higher pressures on request) |
Output |
|
Current output |
|
|
4 … 20 mA |
|
20.8 mA ± 1 % (105 % ± 1 %) |
|
|
|
100 Ω |
|
R max = (UPower Supply – 14 V)/22 mA |
|
NAMUR NE 43 |
|
22 mA (112.5 %) |
|
4 mA |
Digital output |
|
|
HART |
|
FSK |
|
Transmitter |
Pulse Output
(Passive pulse output, needs separate power supply. Pulse output has to be defined in the Option menu Y47 totalizer or energy unit has to be entered. E.g.: 1 pulse/kg or 1 pulse/10 m3) |
|
|
Max. 0.5 Hz |
|
Min. 24 V DC as NAMUR or |
|
open < 1 mA, max. 36 V, closed 100 mA, U < 2 V |
|
open < 1 mA, max. 30 V, closed 100 mA, U < 2 V |
Accuracy |
|
Standard version |
|
|
± 0.75 % |
|
|
|
± 1 % |
|
|
- For steam, gases and liquids
|
± 2 % |
|
|
Pressure and temperature compensated version |
|
|
|
|
± 2 % |
|
± 0.75 % |
|
|
|
± 2.5 % |
|
± 1.5 % |
Repeatability |
± 0.1 % |
Installation conditions
(At different conditions, e.g. installation after control valve, bends or reductions, please refer to the operating instructions.) |
|
|
≥ 20 x DN |
|
≥ 5 x DN |
Software |
|
Uncompensated for gases, steam and liquids, but temperature-compensated for saturated steam |
Select 1 |
Density-compensated by temperature and pressure for superheated steam, no energy calculation |
Select 4 |
Gross heat |
|
When the device has to operate as a energy calculation device |
Select 5 |
In options Y51 to Y56 add information regarding: |
- Y51 Variable current output
- Y52 Power unit
Select one of the following units from power units table in Y52: kJ/h, MJ/h, GJ/h, Btu/h, kcal/h, kW, MW or special (custom)
- Y53 Fullscale power value
- Y54 Variable pulse output
- Y55 Totalizer on/off
- Y56 Configures for totalizer
Select one of the following units from energy units table in Y56: kJ, MJ, GJ, Btu th, kcal, kWh, MWh or special (custom). |
Gases and wet gases |
Select 7 |
Wet gases |
Select Y49 and enter relative humidity in % |
FAD - Free Air Delivery |
|
When the device has to operate close to a compressor |
Select 8 |
In Y81 to Y87 add information regarding: |
- Y81 Inlet suction temperature
- Y82 Atmosphere pressure
- Y83 Pressure drop filter
- Y84 Inlet relative humidity
- Y85 Actual revolutions per minute (of compressor)
- Y86 Rated rpm of compressor
- Y87 Outlet relative humidity. This information is available from compressor supplier.
|
Mixed gases |
When the fluid is a gas mixture, make an SDR request (sheet available on intranet) and fill in gas names and amount in % |
Rated operation conditions |
|
Ambient temperature |
|
|
-40 … +85 °C (-40 … +185 °F) |
|
-40 … +65 °C (-40 … +149 °F) |
Storage temperature |
-50 … +85 °C (-58 … +185 °F) |
Media temperature |
-40 … +240 °C (-40 … +464 °F) |
Density |
Taken into consideration when rating |
Viscosity |
< 10 cP |
Reynold's number |
10 000 … 2 300 000 |
Media pressure limit |
Max. 100 bar (Higher pressure on request. Make an SDR request, sheet available on intranet) |
Design |
|
Material |
|
|
1.4404 (316L)/1.4435 (316L)
Hastelloy C22 available (make an SDR request, sheet available on intranet) |
|
Aluminium
Aluminium (paint petrol) for increased requirement |
- Sensor gaskets: for pick-up and pressure sensor
|
1.4435 (316L)/FPM or FFKM
FPM (Viton®) by steam and non-aggressive gases.
FFKM (Kalrez®) by chlorine and other aggressive gases (only available together with a pressure sensor). |
Process connections |
Flange norm EN 1092-1 form B1/B2 or ASME B16.5 RF.
Other flanges on request. Make an SDR request, sheet available on intranet |
|
DN 15 … 300 (½ … 12") |
|
DN 15 … 100 (½ … 4") |
Degree of protection |
IP66/IP67 |
Dimensions and weights |
See “Dimensional drawings” |
Display and operating interface |
|
Local display |
2 lines, 10 characters per line |
Languages |
German, English, French |
Power supply |
|
|
14 … 36 V DC |
|
14 … 30 V DC |
Certificates and approvals |
|
Explosion protection |
|
|
II 2G EEx d ia [ia] IIC T6 |
|
Class I, II, III, Div 1 & 2 |
Calibration |
All flowmeters will be delivered with a 3 point calibration certificate |
Material Certificate |
Certificate of compliance, pressure test, material certificate, material in acc. of NACE and PMI of pressure bearing metal parts. |
Cleaning |
Choice Cleaning Class1 when fluid is oxygen or contains chloride. |
Certificates |
X-ray test on pressurized weldings and dye penetration test on pressure bearing weldings. |